Instrumentation Cable Standard

Send Inquiry
Instrumentation Cable Standard
Details
Choosing an instrumentation cable is not simply a matter of selecting the correct number of pairs, conductor size, or outer sheath material. In industrial installations, the cable must also meet the electrical, mechanical, environmental, and fire-performance requirements defined by the project...
Category
Instrumentation Cable
Share to
Description

Choosing an instrumentation cable is not simply a matter of selecting the correct number of pairs, conductor size, or outer sheath material. In industrial installations, the cable must also meet the electrical, mechanical, environmental, and fire-performance requirements defined by the project specification. Understanding the relevant instrumentation cable standard helps engineers, contractors, and purchasing teams select a cable that is suitable for its intended signal transmission system.

Instrumentation cables are commonly used to connect field instruments, transmitters, sensors, analyzers, junction boxes, and process control equipment. Depending on the installation, they may require individual pair screening, overall screening, additional mechanical protection, low-smoke properties, or specific fire-performance characteristics.

This guide explains the major standards associated with instrumentation cable design and testing, how these standards relate to cable construction, and what buyers should check before placing an order.

Industrial instrumentation cable with multiple insulated signal conductors pair construction and protective outer sheath

Instrumentation cable construction for industrial measurement, monitoring, and control signal circuits.

1. What Is an Instrumentation Cable Standard?

An instrumentation cable standard is a technical document that defines requirements or test methods for cables used in measurement, monitoring, communication, and process control systems. Depending on the document, it may address conductor characteristics, insulation, cable dimensions, screening, electrical performance, mechanical properties, environmental resistance, and fire behavior.

In practical applications, there is no single standard that automatically covers every feature of every instrumentation cable. A cable may be designed with reference to one standard for its overall construction, another for conductor requirements, and additional standards for flame propagation, smoke emission, or halogen acid gas testing.

For example, an industrial project may specify an instrumentation cable with copper conductors, polyethylene insulation, individual pair screening, an overall screen, and a flame-retardant outer sheath. The project specification should identify the applicable cable standard and the required test methods for each performance characteristic.

Why standards matter when purchasing instrumentation cable

  • Consistent construction: Defined requirements help manufacturers and buyers communicate cable design expectations.
  • Electrical performance: Conductor resistance, insulation characteristics, capacitance, and transmission properties can be evaluated against relevant requirements.
  • Signal integrity: Screening and pair construction can be selected according to the electrical environment and signal requirements.
  • Installation suitability: Mechanical and environmental requirements help determine whether a cable is appropriate for trays, conduits, outdoor routes, or industrial facilities.
  • Fire safety: Separate fire-related standards provide defined test methods for flame propagation, smoke, and combustion gases.
  • Project documentation: Clear standard references make technical review, inspection, and purchasing approval more straightforward.

2. Important Standards Related to Instrumentation Cables

Several international and regional standards may be referenced in instrumentation cable specifications. Their applicability depends on the cable design, intended installation, destination market, and project requirements.

Standard Main Scope Relevance to Instrumentation Cable
EN 50288-7 Multi-element metallic instrumentation and control cables Relevant to cable construction, electrical characteristics, mechanical properties, and test requirements.
EN 50288-1 General requirements for multi-element metallic communication and control cables Provides general provisions used together with applicable sectional specifications.
IEC 60228 Conductors of insulated cables Defines conductor classes and related conductor requirements.
IEC 60332 Tests on electric cables under fire conditions Used to evaluate flame propagation under specified test conditions.
IEC 60754 Tests on gases evolved during combustion of cable materials Relevant when halogen acid gas or acidity requirements are specified.
IEC 61034 Measurement of smoke density of cables burning under defined conditions Relevant to low-smoke cable requirements.
IEC 60331 Tests for circuit integrity under fire conditions Relevant when a project requires a cable to maintain circuit integrity during specified fire exposure.

Important: These standards do not all perform the same function. EN 50288-7 addresses instrumentation and control cable specifications, while IEC 60228, IEC 60332, IEC 60754, and IEC 61034 address particular conductor or cable test requirements. A cable should only be described as compliant with a standard when its actual design and supporting test documentation meet the applicable requirements.

EN 50288-7: Instrumentation and control cable specification

EN 50288-7 is an important reference for multi-element metallic cables used in analogue and digital communication and control applications. Its scope includes instrumentation and control cables used to connect instruments and control systems.

The standard addresses relevant definitions, construction requirements, electrical characteristics, mechanical properties, and test methods. It should be considered together with EN 50288-1, which provides general provisions for the applicable cable family.

For buyers, EN 50288-7 is particularly relevant when specifying multipair or multicore instrumentation cables for industrial process control. However, the exact cable configuration, voltage designation, screening arrangement, and required performance must still be checked against the relevant product specification.

IEC 60228: Conductor requirements

IEC 60228 specifies requirements for conductors of insulated cables. It is commonly referenced when defining the conductor class and electrical characteristics of copper conductors.

Depending on the application and cable design, instrumentation cables may use different conductor constructions:

  • Class 1: Solid conductors, where permitted by the relevant cable specification.
  • Class 2: Stranded conductors for fixed installations.
  • Class 5: Flexible stranded conductors for applications requiring greater conductor flexibility.

The conductor class should be selected according to the applicable cable standard, installation method, termination system, and required mechanical flexibility. A flexible conductor designation alone does not mean that a cable is suitable for continuous movement or repeated bending.

IEC 60332: Flame propagation testing

IEC 60332 covers tests on electric cables under fire conditions. Different parts of the series address different test arrangements, including flame propagation on a single cable and vertical flame spread on bunched cables.

When a project requires flame-retardant instrumentation cable, the buyer should identify the exact IEC 60332 part and test category specified by the project. A statement such as "IEC 60332 compliant" without identifying the applicable test is not sufficiently precise for many technical approvals.

IEC 60754 and IEC 61034: Low-smoke and halogen-related properties

For installations where smoke emission and combustion gas characteristics are important, additional testing may be specified.

  • IEC 60754: Addresses tests on gases evolved during combustion of cable materials. Depending on the part, it evaluates halogen acid gas content or the acidity and conductivity of gases.
  • IEC 61034: Defines a method for measuring smoke density from cables burning under specified conditions.

These test methods are relevant when selecting low-smoke or halogen-free cable designs. However, low smoke emission and low halogen acid gas content are separate properties. A cable should not automatically be described as LSZH merely because it passes one of these tests.

3. BS 5308, PAS 5308 and EN 50288-7: What Buyers Should Know

BS 5308 is a familiar designation in the international instrumentation cable market. Many cable schedules, technical documents, and purchasing specifications still refer to BS 5308 Part 1 or Part 2.

However, its standards status needs careful attention. The original BS 5308 parts were withdrawn and superseded by BS EN 50288-7 in 2005. PAS 5308-1:2009 and PAS 5308-2:2009 were subsequently published to address certain cable constructions, but BSI records show that both PAS documents were withdrawn on 3 April 2024.

This does not mean that every cable previously described using a BS 5308 or PAS 5308 designation is automatically unsuitable. It means that buyers should distinguish between a legacy construction designation, a project-specific requirement, and a currently maintained standard.

Designation Purpose or Background Procurement Consideration
BS 5308 Part 1 Historically associated with polyethylene-insulated instrumentation cables. Withdrawn; confirm the required construction and accepted replacement specification.
BS 5308 Part 2 Historically associated with PVC-insulated instrumentation cables. Withdrawn; do not treat the designation as a current standard without project clarification.
PAS 5308-1:2009 Publicly Available Specification for polyethylene-insulated control and instrumentation cables. Withdrawn by BSI on 3 April 2024.
PAS 5308-2:2009 Publicly Available Specification for PVC-insulated control and instrumentation cables. Withdrawn by BSI on 3 April 2024.
BS EN 50288-7:2005 Sectional specification for instrumentation and control cables. Check the current project edition and applicable general requirements.

When a buyer receives a request for a BS 5308 instrumentation cable, it is advisable to confirm the original part, type, insulation material, screening arrangement, armour requirement, voltage designation, and acceptance criteria. The manufacturer can then determine whether the requested construction can be supplied and which current or project-approved specification applies.

4. How Instrumentation Cable Standards Affect Cable Construction

Standards are not just document references. They influence the way an instrumentation cable is designed, manufactured, tested, and documented. The following construction elements should be considered when preparing a cable specification.

4.1 Copper conductor

The conductor carries measurement and control signals between field equipment and control systems. Conductor material, nominal cross-sectional area, conductor class, and electrical resistance should be defined in the cable specification.

Common instrumentation cable designs use copper conductors. The required conductor size depends on signal characteristics, circuit length, electrical resistance, installation conditions, and the equipment manufacturer's requirements. The appropriate conductor class should also be stated rather than assumed.

4.2 Insulation material

Insulation separates individual conductors and provides the required electrical properties. Depending on the design, instrumentation cable insulation may include PE, PVC, or XLPE.

  • PE insulation: Often selected for its electrical characteristics in signal transmission cable designs.
  • PVC insulation: Used in a range of general-purpose industrial cable constructions.
  • XLPE insulation: Used where the specified electrical, thermal, or environmental requirements call for cross-linked insulation.

The insulation material should be selected based on the applicable cable specification and service conditions. No material should be assumed to be interchangeable without checking the electrical and environmental requirements.

4.3 Twisted pairs and multicore arrangements

Instrumentation cables are available in pair, triad, and multicore configurations. Twisted pairs are widely used for signal circuits because the arrangement can help reduce the effects of external electromagnetic interference when correctly designed and installed.

The number of pairs or cores should match the instrument loop schedule and control system requirements. For example, a two-pair instrumentation cable contains two designated pairs, while a four-core cable does not necessarily provide the same pair grouping or electrical characteristics.

For a more detailed discussion of pair construction and signal-circuit applications, see our 2 Pair Instrument Cable page.

4.4 Individual and overall screening

Screening is an important consideration where instrumentation signals may be affected by electromagnetic interference from motors, variable frequency drives, power cables, switching equipment, or other electrical sources.

Depending on the application, a cable may use:

  • Individual pair screening: Each pair has its own screen to help limit interference between circuits and from external sources.
  • Overall screening: A common screen surrounds the laid-up cable elements.
  • Individual and overall screening: Combines pair-level and collective screening for projects with more demanding signal separation requirements.

Screening materials and grounding arrangements must be defined in the cable and installation specifications. The presence of a screen alone does not guarantee effective EMC performance. Correct screen termination, bonding, routing, and grounding practices are also important.

For additional information about screened cable construction, see our Shielded Control Cable page.

4.5 Outer sheath and mechanical protection

The outer sheath protects the internal cable elements against the installation environment. PVC, PE, and LSZH compounds may be considered according to the required mechanical, chemical, temperature, smoke, and halogen-related properties.

Where cables are exposed to mechanical damage, an armoured design may be required. Armour type and material should be selected according to the installation method and project specification. Armour should not be confused with an electromagnetic screen, as the two layers serve different functions.

Instrumentation cable cutaway showing copper conductors insulation twisted pairs screening options and outer sheath as illustrative construction elements

Illustrative instrumentation cable elements. Actual conductor count, insulation, screen and armour configuration depend on the approved product design.

5. Common Tests for Instrumentation Cable Compliance

Testing verifies whether a cable meets the technical requirements defined by its product standard and purchase specification. The required tests depend on the cable design and project conditions.

Test Category What It Evaluates Why It Matters
Conductor resistance Electrical resistance of the conductor. Helps verify conductor characteristics and electrical performance.
Insulation resistance Resistance of the insulation between conductors or between conductors and other specified elements. Helps evaluate insulation condition.
Voltage test Electrical withstand performance under specified test conditions. Verifies insulation performance against the applicable requirements.
Capacitance test Capacitance between specified conductors or circuit elements. Relevant to signal transmission characteristics and circuit design.
Flame propagation test Behavior of a cable under a defined flame exposure. Supports verification of specified flame-retardant performance.
Smoke density test Smoke emission under defined combustion conditions. Relevant to low-smoke requirements.
Halogen acid gas test Gas characteristics produced during combustion of cable materials. Relevant to specified halogen-related requirements.
Dimensional and visual inspection Construction dimensions, workmanship, marking, and visible defects. Helps confirm product consistency with the approved design.

Not every cable requires every test listed above. Buyers should request the applicable inspection and test plan, routine test records, and type-test evidence where required by the project. Test methods, sample requirements, acceptance limits, and document formats should be agreed before production.

6. How to Select an Instrumentation Cable According to Standards

Choosing a compliant cable starts with the actual operating conditions rather than the standard number alone. The following points help engineers and procurement teams prepare a more complete technical inquiry.

Step 1: Identify the signal and circuit requirements

Determine whether the cable will be used for analogue signals, digital signals, control circuits, or other instrumentation functions. Confirm the number of circuits, pairs, triads, or cores required by the instrument and control system drawings.

Step 2: Confirm the required cable standard

Identify the standard and edition stated in the project specification. If a document references BS 5308 or PAS 5308, confirm whether the project requires that legacy designation or accepts an alternative construction based on an applicable current specification.

Step 3: Define the electrical construction

Specify conductor material, conductor size, conductor class, insulation type, voltage designation, and any relevant electrical transmission requirements. Do not rely on a generic product name to define these details.

Step 4: Choose the screening arrangement

Review the electromagnetic environment, signal sensitivity, cable routing, and grounding strategy. Decide whether individual pair screening, overall screening, or combined screening is required.

Step 5: Evaluate fire and environmental requirements

Check whether the installation requires flame-retardant, fire-resistant, low-smoke, halogen-free, oil-resistant, UV-resistant, or other environmental properties. These characteristics should be linked to specific test methods or project requirements.

Step 6: Confirm mechanical protection and installation conditions

Determine whether the cable will be installed indoors, outdoors, in cable trays, conduits, underground ducts, or areas with potential mechanical damage. Confirm whether armour or additional protective measures are necessary. For moving applications, verify the required flexing performance separately.

Step 7: Review documentation before approval

Request a technical datasheet, construction drawing, applicable standard references, routine test information, and required type-test reports or certificates. Confirm that the documentation describes the exact cable configuration being offered.

7. Information to Include in an Instrumentation Cable Specification

A clear technical specification reduces misunderstandings between the project engineer, cable manufacturer, purchasing department, and installation contractor. The following information can be used as a starting point for an instrumentation cable inquiry.

Specification Item Information to Confirm
Applicable standard Standard number, edition, amendments, and project-specific requirements.
Application Analogue signal, digital signal, measurement, monitoring, or control circuit.
Number of elements Number of pairs, triads, or cores.
Conductor Material, nominal cross-sectional area, and conductor class.
Insulation PE, PVC, XLPE, or another specified compound.
Screening Unscreened, individual pair screen, overall screen, or combined screen.
Drain wire Required material, size, and arrangement, if applicable.
Outer sheath Material, color, and required environmental performance.
Armour Armour type, material, and protection requirements, if applicable.
Fire performance Required IEC 60332 test part or other project-defined fire criteria.
Smoke and gas performance Applicable IEC 61034 and IEC 60754 requirements, where specified.
Testing and documents Routine tests, type tests, inspection plan, datasheet, and certificates required.

8. Applications of Standard-Compliant Instrumentation Cables

Instrumentation cables are used across industries where reliable signal connections are required between field devices and control equipment. The exact cable construction and applicable standards depend on the operating environment.

  • Oil and gas facilities: Connecting pressure transmitters, temperature sensors, flow meters, and process monitoring devices.
  • Petrochemical plants: Carrying measurement and control signals between field instruments, junction boxes, and distributed control systems.
  • Power generation: Connecting monitoring equipment, sensors, and control circuits in power plants and associated facilities.
  • Water and wastewater treatment: Linking level sensors, flow meters, analyzers, and remote monitoring systems.
  • Manufacturing facilities: Connecting industrial sensors, automation equipment, and process control systems.
  • Building and infrastructure systems: Supporting specified monitoring and control functions in technical installations.

For hazardous areas, intrinsically safe circuits, or installations with special fire and environmental requirements, the cable specification must be coordinated with the complete system design and applicable local regulations. A cable standard alone does not establish that an entire installation is suitable for a hazardous area.

9. Why Review the Complete Cable Specification Instead of Only the Standard Number?

Two instrumentation cables may both refer to the same general standard while having different conductor sizes, insulation materials, pair arrangements, screens, sheath compounds, or armour configurations. These differences can affect electrical performance, installation suitability, and service life.

For example, a screened multipair cable intended for a process control system is not automatically interchangeable with an unscreened multicore cable. Likewise, a flame-retardant cable is not necessarily a fire-resistant cable capable of maintaining circuit integrity during a fire.

When reviewing a quotation, compare the complete construction and test requirements rather than checking only the standard designation. This is especially important when a project specification contains older references, customer-specific requirements, or multiple standards covering different cable properties.

10. Frequently Asked Questions About Instrumentation Cable Standards

What is the main standard for instrumentation cable?

EN 50288-7 is an important sectional specification for multi-element metallic instrumentation and control cables. It should be used together with the applicable general requirements in EN 50288-1. Other standards may be required for conductor properties, fire performance, smoke emission, or combustion gas characteristics.

Is BS 5308 still a current instrumentation cable standard?

The original BS 5308 parts were withdrawn and superseded by BS EN 50288-7 in 2005. PAS 5308-1:2009 and PAS 5308-2:2009 were also withdrawn by BSI on 3 April 2024. The BS 5308 designation is still encountered in project documents and purchasing specifications, so buyers should confirm the required construction and acceptance criteria.

Does IEC 60228 apply to instrumentation cable conductors?

IEC 60228 is commonly referenced for conductor requirements in insulated cables. The conductor material, size, class, and resistance requirements should be confirmed against the applicable instrumentation cable specification.

What is the difference between flame-retardant and fire-resistant instrumentation cable?

Flame-retardant performance relates to limiting flame propagation under specified test conditions. Fire-resistant performance concerns maintaining circuit integrity under defined fire exposure conditions. The required test standard and performance criteria should be stated separately in the project specification.

Does every instrumentation cable need a screen?

No. Screening requirements depend on the signal type, electrical noise environment, cable routing, and system design. Individual pair screening, overall screening, and combined screening are different construction options and should be selected according to the project requirements.

What documents should be requested from an instrumentation cable manufacturer?

Typical documents include a technical datasheet, cable construction drawing, applicable standards list, routine test records, and relevant type-test reports or certificates where required. The documents should correspond to the actual cable construction and specified performance.

Can a cable comply with multiple instrumentation cable standards?

A cable can be designed and tested against multiple applicable standards or test methods, provided its construction meets the relevant requirements. However, the manufacturer should identify exactly which standard applies to each part of the design and which tests have been completed.

Conclusion: Specify Instrumentation Cable by Construction, Performance and Standards

Selecting an instrumentation cable requires more than choosing a product name or referring to a single standard number. EN 50288-7, IEC 60228, IEC 60332, IEC 60754, and IEC 61034 address different aspects of cable design and performance. Understanding their respective roles helps buyers prepare more accurate technical specifications and evaluate cable quotations more effectively.

Before approving an instrumentation cable, confirm its conductor configuration, insulation, screening, sheath, mechanical protection, fire requirements, and test documentation. A complete and clearly defined specification makes it easier to select a cable that matches the intended industrial application.

Hot Tags: instrumentation cable standards、instrumentation cable specification、EN 50288-7 cable、IEC instrumentation cable、instrumentation cable testing、industrial instrumentation cable、BS 5308 instrumentation cable、instrumentation cable compliance, 1 pair instrument cable, 4 core instrument cable, 4 wire instrument, Armoured Instrumentation Cable, instrument pair cable, instrumentation cable