Model Interpretation
|
Model Code |
Meaning |
|
WD |
Low Smoke Zero Halogen (LSZH) |
|
ZA |
Flame Retardant Grade A |
|
YJ |
XLPE (Cross-linked Polyethylene) Insulation |
|
Y |
Polyolefin Sheath (LSZH Sheath) |
|
23 |
Double Steel Tape Armored |
|
0.6/1kV |
Rated Voltage 0.6/1kV |
|
3×120+1×70 |
3 cores × 120mm² main conductors + 1 core × 70mm² neutral/earth conductor |
WDZA-YJY23 is a Low Smoke Zero Halogen (LSZH), Flame Retardant Grade A, XLPE insulated, double steel tape armored power cable designed for low-voltage power transmission and distribution systems. It combines flame retardancy, low smoke zero halogen performance, and mechanical protection.
Cable Construction
- Typical cable structure:
Copper Conductor → XLPE Insulation → Filling → Wrapping Tape → Inner Sheath → Double Steel Tape Armor → LSZH Outer Sheath
- Copper Conductor: Excellent electrical conductivity, typically using Class 2 stranded copper conductor.
- XLPE Insulation: Superior electrical properties, high temperature resistance, and long service life.
- Double Steel Tape Armor: Enhanced compression resistance, impact resistance, and mechanical protection.
- LSZH Outer Sheath: Low smoke and no corrosive halogen gases during combustion.
Specification Description
3×120+1×70mm² means 3 × 120mm² main conductors for three-phase power supply (L1/L2/L3).
1 × 70mm² auxiliary conductor is typically used as Neutral (N) or Protective Earth (PE).
This is a typical 3+1 core low-voltage power cable configuration.
Technical Parameters (Typical Values)
| Parameter | Specification |
|---|---|
| Rated Voltage | 0.6/1kV |
| Conductor Material | Copper, Class 2 Stranded Conductor |
| Insulation Material | XLPE (Cross-linked Polyethylene) |
| Sheath Material | LSZH Polyolefin |
| Maximum Operating Temperature | 90°C |
| Short Circuit Temperature | Max. 250°C (up to 5 seconds) |
| Installation Temperature | Not lower than 0°C |
| Minimum Bending Radius | ≥ 15 × Cable Diameter (D) |
| Flame Retardant Grade | ZA (Class A) |
| Installation Method | Cable tray, cable trench, conduit, or protected underground installation |
Product Features
- Low Smoke Zero Halogen (LSZH): Produces minimal smoke and no corrosive halogen gases during fire.
- Flame Retardant Grade A: Reduces flame propagation risk.
- High Mechanical Protection: Double steel tape armor resists compression and impact.
- Heat Resistance & Long Service Life: Continuous conductor operating temperature up to 90°C.
Applications
High-rise buildings, hospitals, schools, shopping malls, airports, subways, tunnels, data centers, commercial complexes, industrial plants, and underground cable installations.
Full Product Name
Flame Retardant Grade A Low Smoke Zero Halogen XLPE Insulated Polyolefin Sheathed Double Steel Tape Armored Power Cable, Rated Voltage 0.6/1kV, 3×120mm² + 1×70mm².
Hot Tags: wdza-yjy23-0.6/1kv 3×120+1×70 lszh cable, China wdza-yjy23-0.6/1kv 3×120+1×70 lszh cable manufacturers, suppliers, factory